Performance assessment of oxidants as a biocide for biofouling control in industrial seawater cooling towers
- Publication Type:
- Journal Article
- Citation:
- Journal of Industrial and Engineering Chemistry, 2018, 59 pp. 127 - 133
- Issue Date:
- 2018-03-25
Closed Access
Filename | Description | Size | |||
---|---|---|---|---|---|
1-s2.0-S1226086X17305543-main.pdf | Published Version | 1.74 MB |
Copyright Clearance Process
- Recently Added
- In Progress
- Closed Access
This item is closed access and not available.
© 2017 The Korean Society of Industrial and Engineering Chemistry Biofouling can significantly hamper the efficiency of seawater cooling towers. The aim of this study was to investigate the effectiveness of alternative oxidants (i.e. ozone (O3) and chlorine dioxide (ClO2)) comparing with commonly being used chlorine in biofouling control. Effects of cycle of concentration, temperature and oxidant dosage along with residual decay and kinetics were studied. Even at lower oxidant dosage (total residual oxidant equivalent = 0.1 mg/l Cl2), ClO2 showed a better disinfection effect compared to chlorine and O3. Results of bench-scale studies will be helpful in the selection of appropriate oxidant for seawater cooling tower operation.
Please use this identifier to cite or link to this item: